ALIENCULTIST.COM
HARDWARE ARCHIVES // PART RECORD

[ POWER CONVERSION // IDENTIFIED MODEL ]

HPE 3200 W M-CRPS Titanium Hot Plug PSU Kit (P67248-B21)

Exact module identity: HPE P67248-B21. This record applies only to this manufacturer option/PID; nominal wattage or a similar shell does not prove cross-model compatibility.

Original local block schematic for HPE 3200 W M-CRPS Titanium Hot Plug PSU Kit (P67248-B21), not a circuit or pinout
LOCAL ORIGINAL BLOCK SCHEMATIC // NOT TO SCALE

HIGH-VOLTAGE WARNING: Disconnect mains before external inspection. Never open a PSU. Internal capacitors may retain lethal charge after unplugging. Do not probe or repair its interior; use qualified service or replace the unit.

Model-specific ratings & fit

Manufacturer identity / exact moduleHPE P67248-B21 — HPE 3200 W M-CRPS Titanium Hot Plug PSU Kit (P67248-B21)
Rated output / rail information3200 W high-line class / 1600 W at 100–127 V low-line; +12 VDC main output (3200 W class; use nameplate/QuickSpecs for exact current limit); standby rail per module specification.
AC input100–127 V AC and 200–240 V AC, 50/60 Hz; 277 V AC or 380 V DC only on specifically qualified systems.
Efficiency80 PLUS Titanium; up to 96% (manufacturer rating)
Form factor / mountingHPE M-CRPS hot-plug module, 73.5 mm class; not ATX.
Connectors / backplaneIEC C20 AC inlet; HPE M-CRPS blind-mate output into a supported power bay/backplane.
System compatibilityOnly HPE Gen12/Alletra/XD230 systems that list P67248-B21 and support its input mode and wide M-CRPS bay. 277 V AC and 380 V DC are restricted to specifically qualified host configurations.
Redundancy / coolingHot-plug/redundancy is host-managed and conditional on remaining capacity. Do not remove a module unless host status and service procedure confirm a safe redundant state.
Revision distinctions3200 W class at qualified high-line inputs; 1600 W low-line ceiling. Input alternatives (277 V AC / 380 V DC) are not universal. Match exact part, host, feed and bay.

Compatibility & safe installation

  • Confirm full manufacturer part/PID, revision and label against the host’s exact system QuickSpecs, service manual and power-supply matrix.
  • Check input voltage, rail limits, connector/backplane keying, bay dimensions, supported efficiency class and cooling direction before installation.
  • Hot-plug is conditional: verify healthy remaining supply capacity, supported redundancy state and the host service procedure before removing a live module.
  • Do not mix modules or use modular leads across models unless the system manufacturer explicitly approves that combination.
  • Never open or probe a PSU. Retire damaged, wet, burnt, corroded, modified or unidentified units.

Revision & archival notes

3200 W class at qualified high-line inputs; 1600 W low-line ceiling. Input alternatives (277 V AC / 380 V DC) are not universal. Match exact part, host, feed and bay.

Archive a clear nameplate photograph, complete option/FRU number, hardware revision, AC inlet and connector labels, host model, and source-document revision. Distinguish manufacturer ratings from derived values.

Manufacturer references

  1. HPE 3200W M-CRPS Titanium Hot Plug Power Supply Kit data sheetExact option identity, input modes, low-line derating and efficiency.
  2. HPE 3200 W M-CRPS Titanium Hot-plug Power Supply | HPE ProLiant Compute documentationHost-qualified input modes and supported system requirements.
  3. HPE ProLiant Compute DL320 Gen12 User Guide — installing an AC power supplyExample host hot-plug procedure and safety; the 3200 W kit is not implied compatible with this example server.

Manufacturer nameplate and applicable system manual take precedence over this summary.