[ THREE-PHASE ENERGY METER // 120 A CT KIT ]

Shelly Pro 3EM

DIN-rail three-phase meter, model SPEM-003CEBEU, documented with the 120 A CT kit. The meter's communications do not make it a switched rack PDU or protective relay.

Original three-phase schematic for Shelly Pro 3EM and current transformers
LOCAL FUNCTIONAL SCHEMATIC // NOT A WIRING DIAGRAM

VARIANT CONTROL: Shelly offers different Pro 3EM revisions and CT packages. This record names the 120 A CT package; verify that the supplied sensors and order code match the unit before use.

Specifications & compatibility

Exact model / functionShelly Pro 3EM, SPEM-003CEBEU, 120 A CT package; three-phase energy metering.
Measured metricsPer-phase voltage, current, active and apparent power, and energy; documented active energy accuracy class B.
Voltage / phaseThree-phase system; published operating/supply range 100–260 V. Confirm the wiring topology and per-phase limits in the exact revision manual.
Current range / accuracyPackage includes 120 A CTs. The 120 A value is sensor capacity, not direct-current input. Active-energy measurement class B; do not infer other instrument accuracies from this energy class.
Display / network / outputNo measurement display. Ethernet, Wi-Fi and Bluetooth; local web interface, Modbus TCP and documented HTTP/MQTT integration. Verify firmware support.
Form factorDIN-rail electronic meter with external current transformers.
Host compatibilityShelly app, local network clients and compatible Modbus TCP, HTTP or MQTT hosts. No OS-specific desktop requirement is listed.
Electrical safetyUse only the manual's voltage, phase and CT wiring instructions. Installation is for a qualified person with the panel safely isolated; communications and metering are not overcurrent protection or an isolation method.

Installation & archival notes

  • Record phase configuration, CT ratio/orientation, full model code and firmware with readings.
  • Do not assume a CT kit from another Pro 3EM revision is interchangeable.
  • Never work on exposed energized conductors; obey local electrical codes and sensor instructions.