[ NETWORKED / SWITCHED RACK PDU // EXACT SKU ]
Eaton Managed Rack PDU EMA326-10
200–240 V three-phase, 30 A L15-30P input (24 A operating load); 18 C13 + 6 C19 managed outlets; 0U. This static record covers the named model only; confirm complete regional suffix, revision and nameplate before installation.
ARCHIVAL IDENTIFICATION: EMA326-10. Record the complete label, serial/date code, firmware and condition; similarly named models are not electrically interchangeable.
Exact model specifications
| SKU / topology | EMA326-10 — networked switched rack power distribution unit; no UPS battery or stored runtime. |
|---|---|
| Input and output voltage | 200–240 V AC input and output (3-phase supply; confirm the system voltage/nameplate) |
| Phase / ampacity | Three phase; 30 A input connector class, 24 A maximum operating load; 8.64 kW class at 208 V three-phase. |
| Outlet count and type | 24 total: 18 × IEC 60320 C13 and 6 × IEC 60320 C19 |
| Metering / outlet switching | Managed/switched ePDU with outlet-level remote control and metering; confirm per-outlet monitoring/control scope from the selected firmware/specification revision. |
| Network management | Ethernet network management and remote switching/monitoring; Eaton ePDU management software and network protocols vary by controller/firmware. |
| Rack dimensions | 0U vertical rack installation; full-height format, mounted along rack side rails. Confirm length, depth and clearances from the model installation documentation. |
| Plug and load compatibility | NEMA L15-30P three-phase input plug; requires matching grounded 200–240 V three-phase L15-30R service. C13 accepts C14 and C19 accepts C20 equipment inlets; verify phase/voltage for each load. |
| Electrical safety | Match the three-phase source, connector, phase sequence and protective-earth arrangement to the complete nameplate and local electrical code; 24 A is the stated operating load, not 30 A continuous. Do not use adapters or energize with damaged connectors. Installation by a qualified electrician. |
Service and safe deployment
- Verify voltage, phase, inlet plug, circuit ampacity, continuous load and per-outlet ratings against the PDU nameplate and the exact product manual.
- Use grounded, correctly protected service; never defeat the protective-earth conductor, overload an outlet/bank, or daisy-chain power strips/PDUs.
- Mount the chassis using the manufacturer-approved brackets and preserve ventilation and strain relief. Inspect cord, plugs, receptacles and enclosure for heat, wear or damage.
- Disconnect upstream power before installation, relocation or service. Do not open energized mains equipment; use a qualified electrician where required.
- Network management can switch power to connected systems; isolate management access, set unique credentials and verify firmware before deployment.
Manufacturer sources and manual
- Manufacturer product page — Eaton Managed Rack PDU EMA326-10Manufacturer model listing and configuration details; match the complete SKU and region. Original page is gone; this is the Internet Archive’s copy.
- Manufacturer documentation — EMA326-10 manufacturer specifications and technical dataManufacturer manual, technical data or specifications; use the revision applicable to the unit label and follow its installation and safety directions. Original page is gone; this is the Internet Archive’s copy.