Eaton 9SX 1500i

230 V online UPS, 1500 VA / 1350 W, IEC outlets, network-card option. The specifications below are for this named model and region only; verify the complete product label and matching manual before deployment or service.

Original local functional schematic for Eaton 9SX 1500i, not a product photograph
LOCAL FUNCTIONAL SCHEMATIC // NOT TO SCALE

ARCHIVAL IDENTIFICATION: Preserve the complete SKU, suffix, region, date code, revision, installed battery part (if present), firmware and physical condition. Similar model names do not establish hardware equivalence.

Specifications, conditions & service

Catalog subcategoryOnline UPS
Topology / power pathOnline double-conversion (VFI): rectifier and inverter continuously condition output; battery supports the DC link during mains failure.
Ratings / output configuration1500 VA / 1350 W; 230 V regional SKU. Eight IEC C13 outputs on the 9SX1500i configuration. Check the exact product suffix/label for outlet and input details.
Battery / replaceabilityInternal sealed lead-acid battery; 9SX series supports battery replacement/service as documented. Use only Eaton-listed pack and procedure.
Runtime / limits and conditionsEaton runtime graphs are load dependent; use the graph for 9SX1500i and actual watts. Runtime varies with battery age/condition, charge, ambient temperature and any approved external modules; do not transfer estimates from another rating.
Interfaces / monitoringLCD; USB and RS-232; communication slot supports compatible optional network/relay cards. Confirm card, cable and host software compatibility.
Safety / installation caveats230 V only. Observe 1350 W and IEC outlet limits. Online conversion has continuous conversion losses/heat; provide specified ventilation. Battery replacement does not make opening an energized chassis safe.
Model variants / revision checks9SX1500i is distinct from 9SX1500 (other region) and 9SX1500IRT; connector set and battery/accessory configuration differ by SKU.

Field service / archive notes

  • Record labels and connector layout before installation; document load, input conditions, measured behavior and test date separately from manufacturer-rated values.
  • Never open energized mains equipment. Battery devices can retain dangerous voltage or high fault current; follow the manufacturer’s replacement and recycling procedure.
  • Inspect enclosure, cord, plugs, grounding, indicators, alarms and battery condition. Quarantine damaged, swollen, leaking or heat-affected equipment.
  • Network-management appliances should be isolated, updated where supported and configured with non-default credentials; do not expose legacy management interfaces directly to the public internet.

Manufacturer references

  1. Manufacturer product listing — Eaton 9SX 1500iModel identity and product-family specification reference. Confirm exact regional SKU against the chassis label.