ALIENCULTIST.COM
HARDWARE ARCHIVES // MODEL RECORD

[ ONLINE DOUBLE-CONVERSION UPS // IDENTIFIED MODEL ]

Eaton 9PX3000RT

Eaton 9PX3000RT: 3000 VA / 2700 W online double-conversion UPS. This record covers only the identified SKU and regional configuration; match complete model code and nameplate to manufacturer documentation.

Original local functional schematic for 9PX3000RT, not a product photograph or wiring diagram
LOCAL FUNCTIONAL SCHEMATIC // NOT TO SCALE

ARCHIVAL IDENTIFICATION: Record full SKU, region, serial/date code, firmware/revision, installed options, battery identifier and observed condition. Similar product names do not prove electrical compatibility.

Model specifications

Exact model / topologyEaton 9PX3000RT; Online double-conversion UPS; sine-wave output.
Rated output3000 VA / 2700 W. VA and W limits are separate constraints; never exceed either.
Input / output voltageInput: 120 V nominal, North American model. Output: Configurable nominal output; verify selected setting and load compatibility in the owner’s manual.
Input connectionNEMA L5-30P input plug.
Output receptacles6 × NEMA 5-20R plus 1 × NEMA L5-30R output receptacles.
Battery chemistry / serviceInternal sealed lead-acid battery pack; battery replacement and approved external battery compatibility are model-specific. Use the documented procedure only.
RuntimeEaton’s 9PX 700–3000 VA 2U owner’s manual provides load-dependent runtime information; actual runtime varies with load, battery condition/age, charge, environment and external battery configuration.
Transfer behaviorOnline double-conversion operation continuously supplies regulated inverter output; normal operation does not wait for a mains failure to transfer to inverter. Bypass/overload behavior is defined in the owner’s manual.
Communications / compatibilityLCD/status, USB and serial communications; compatible optional network management card/relay accessories may be used. Check current Eaton software, card and host support.
Compatibility / safety120 V 30 A input circuit with L5-30R source for the UPS L5-30P plug. Match connected plugs and outlet-specific limits; 2700 W is the total maximum. Follow grounding, ventilation and battery safety directions. Read the exact revision of the manufacturer manual before connection, service or battery replacement.

Service and compatibility notes

  • Measure and record connected watts and source voltage; runtime is not guaranteed for an aged or untested battery.
  • Do not open energized mains equipment. Never defeat protective earth, overload an outlet, use damaged equipment, or substitute an unapproved battery.
  • For hardwired or high-current versions, qualified installation, rated branch protection and local electrical code apply.
  • Confirm the complete model suffix, input wiring, output voltage, outlet map and manual revision against the unit nameplate before connecting equipment.

Manufacturer datasheet and manual sources

  1. Eaton 9PX3000RT manufacturer SKU specificationOfficial SKU identity and product specifications.
  2. Eaton 9PX 700–3000 VA 2U owner’s manualOfficial manufacturer owner’s manual for installation, runtime, batteries, communications and safety.