ALIENCULTIST.COM
HARDWARE ARCHIVES // PART RECORD

[ THREE-PHASE CT ENERGY METER // SDM630MCT V2 ]

Eastron SDM630MCT V2

Three-phase multifunction DIN-rail meter using current transformers. This record is for the RS485 Modbus CT-operated V2, distinct from Mbus, pulse and multi-tariff variants.

Original three-phase schematic of Eastron SDM630MCT V2 and CTs
LOCAL FUNCTIONAL SCHEMATIC // NOT A WIRING DIAGRAM

VARIANT CONTROL: Nominal voltage and auxiliary supply vary by order variant. Confirm the exact nameplate, supply option, CT ratio and revision before connecting.

Specifications & compatibility

Exact model / functionEastron SDM630MCT V2, RS485 Modbus, CT-operated three-phase multifunction energy meter.
Measured metricsVoltage, current, frequency, active/reactive/apparent power, power factor, demand and bidirectional active/reactive energy.
Voltage / phaseThree-phase, four-wire; nominal 3 × 230/400 V AC. Operating voltage is 80–120% of nominal; auxiliary supply varies by exact version.
Current range / accuracyExternal CT secondary 1 A or 5 A; set the primary ratio for the installed CT. Standard active-energy accuracy is Class 1; MID variants specify their own class and are not interchangeable.
Display / network / outputLCD; RS485 Modbus RTU and pulse output, with register/output behavior defined by the model manual.
Form factorDIN-rail mounted enclosure for a three-phase distribution or control panel.
Host compatibilityRS485 Modbus RTU-compatible host, PLC, logger or building monitor; no operating-system-specific host requirement.
Electrical safetyInstall according to the exact V2 manual and local electrical code. Match the CT secondary, polarity, phase and auxiliary supply; use qualified electrical personnel and isolate circuits before wiring.

Installation & archival notes

  • Document nominal voltage, auxiliary supply, CT ratio, phase configuration, communication settings and manual revision.
  • Do not connect CT secondary wiring using instructions for the direct-measurement SDM630 variant.
  • Metering does not provide overcurrent protection or electrical isolation.

Manufacturer sources

  1. Eastron — SDM630MCT product pageModel family, CT operation and interface information.
  2. Eastron — SDM630MCT series datasheetInput, supply and measurement specifications; choose the matching V2 variant.
  3. Eastron — SDM630MCT V2 family user manualModel-revision wiring, configuration and operating limits.