Eastron SDM120CTM

Compact single-phase DIN-rail meter with external current transformer input, LCD readout and RS485 Modbus RTU. This is the Modbus CT model, not the Mbus or pulse-only variant.

Original diagram of Eastron SDM120CTM DIN-rail energy meter and CT input
LOCAL FUNCTIONAL SCHEMATIC // NOT A WIRING DIAGRAM

IDENTIFICATION: Record the CT primary ratio and 1 A or 5 A secondary selected in the meter configuration; an incorrect ratio invalidates readings.

Specifications & compatibility

Exact model / functionEastron SDM120CTM, single-phase multifunction energy meter, CT-operated RS485 Modbus version.
Measured metricsActive and reactive energy, voltage, current, active/reactive/apparent power, power factor, frequency and demand.
Voltage / phase230 V nominal single-phase; operating range 176–276 V AC in the cited series datasheet.
Current range / accuracyExternal CT secondary 1 A or 5 A; set the CT ratio for the installed sensor. Active energy Class 1 and reactive energy Class 2 per manufacturer series specifications.
Display / network / outputBacklit LCD; RS485 Modbus RTU and pulse output. Check the selected register map and pulse configuration in the manual.
Form factor18 mm DIN-rail enclosure for a distribution board or control cabinet.
Host compatibilityAny properly configured RS485 Modbus RTU host or data logger; no host operating system is required by the meter.
Electrical safetyMeter input, CT secondary and auxiliary terminals must be wired as in the model manual. Use a qualified installer, isolate before work, and never open-circuit an energized CT secondary unless its instructions explicitly permit it.

Installation & archival notes

  • Keep exact CT ratio, phase assignment, communication address and baud rate with every export.
  • Do not apply the direct-connected SDM120 model's current range to this CT-operated variant.
  • Use overcurrent protection and enclosure practices required by the installation; the meter itself is not a protective device.

Manufacturer sources

  1. Eastron — SDM120CTM product pageModel identity, interface and measurement overview.
  2. Eastron — SDM120CT series datasheetElectrical operating range, input configuration and accuracy class.
  3. Eastron — SDM120CTM user manualRS485 setup, CT ratio configuration and safety-critical wiring instructions.