[ NETWORKED / SWITCHED RACK PDU // EXACT SKU ]

CyberPower PDU41105 Switched PDU

200–240 V single-phase, L6-30P 30 A input (24 A continuous); 21 C13 + 3 C19 switched outlets; 0U. This static record covers the named model only; confirm complete regional suffix, revision and nameplate before installation.

Original local schematic of CyberPower PDU41105 Switched PDU; not a product photo or wiring diagram
LOCAL FUNCTIONAL SCHEMATIC // NOT TO SCALE

ARCHIVAL IDENTIFICATION: PDU41105. Record the complete label, serial/date code, firmware and condition; similarly named models are not electrically interchangeable.

Exact model specifications

SKU / topologyPDU41105 — networked switched rack power distribution unit; no UPS battery or stored runtime.
Input and output voltage200–240 V AC input and output
Phase / ampacitySingle phase; 30 A input, 24 A maximum continuous load (derated)
Outlet count and type24 total: 21 × IEC 60320 C13 and 3 × IEC 60320 C19; individually switched
Metering / outlet switchingOutlet switching/reboot and real-time input/outlet monitoring; LCD display, power sequencing and per-bank protection.
Network managementRJ45 Ethernet management with web/SNMP monitoring and outlet control; optional sensor input and notifications are firmware/configuration dependent.
Rack dimensions0U vertical rack-mount form factor; full-height unit mounted in rack side channel. Confirm overall length, rail fit and clearance against the user manual for the exact revision.
Plug and load compatibilityAttached NEMA L6-30P requires a grounded 200–240 V single-phase L6-30R circuit. IEC C13 mates with C14 and C19 with C20 equipment inlets; verify equipment input voltage.
Electrical safetyContinuous load limited to 24 A on a 30 A input; comply with branch protection and outlet-bank ratings. 200–240 V output is unsuitable for 120 V-only equipment. Maintain earth continuity; disconnect upstream power before installation/service.

Service and safe deployment

  • Verify voltage, phase, inlet plug, circuit ampacity, continuous load and per-outlet ratings against the PDU nameplate and the exact product manual.
  • Use grounded, correctly protected service; never defeat the protective-earth conductor, overload an outlet/bank, or daisy-chain power strips/PDUs.
  • Mount the chassis using the manufacturer-approved brackets and preserve ventilation and strain relief. Inspect cord, plugs, receptacles and enclosure for heat, wear or damage.
  • Disconnect upstream power before installation, relocation or service. Do not open energized mains equipment; use a qualified electrician where required.
  • Network management can switch power to connected systems; isolate management access, set unique credentials and verify firmware before deployment.

Manufacturer sources and manual

  1. Manufacturer product page — CyberPower PDU41105 Switched PDUManufacturer model listing and configuration details; match the complete SKU and region.
  2. Manufacturer documentation — PDU41105 User ManualManufacturer manual, technical data or specifications; use the revision applicable to the unit label and follow its installation and safety directions.