ALIENCULTIST.COM
HARDWARE ARCHIVES // MODEL RECORD

[ NETWORKED / SWITCHED RACK PDU // EXACT SKU ]

CyberPower PDU41023 Switched PDU

120 V single-phase, L5-30P 30 A input (24 A continuous), 16 switched NEMA 5-20R outlets; 1U. This static record covers the named model only; confirm complete regional suffix, revision and nameplate before installation.

Original local schematic of CyberPower PDU41023 Switched PDU; not a product photo or wiring diagram
LOCAL FUNCTIONAL SCHEMATIC // NOT TO SCALE

ARCHIVAL IDENTIFICATION: PDU41023. Record the complete label, serial/date code, firmware and condition; similarly named models are not electrically interchangeable.

Exact model specifications

SKU / topologyPDU41023 — networked switched rack power distribution unit; no UPS battery or stored runtime.
Input and output voltage100–120 V AC input; 100–120 V AC output
Phase / ampacitySingle phase; 30 A input, 24 A maximum continuous load (80% derating)
Outlet count and type16 × NEMA 5-20R (eight front, eight rear); individually switched
Metering / outlet switchingInput voltage/current/power metering at the LCD and over the management interface; individual or grouped outlet switching.
Network managementRJ45 Ethernet network management; web/SNMP access and event alerts supported by the installed management firmware.
Rack dimensions1U horizontal rackmount; approximately 17.1 × 8.5 × 1.8 in (W×D×H), 19-inch rack compatible.
Plug and load compatibilityAttached NEMA L5-30P twist-lock plug. Requires a matching grounded 120 V single-phase L5-30R branch receptacle and circuit; NEMA 5-20R outputs accept 5-15P/5-20P loads only within branch and per-outlet ratings.
Electrical safety30 A inlet does not mean 30 A continuous load: limit continuous load to 24 A and follow branch-breaker and outlet-bank limits. Maintain protective earth, do not use improvised adapters, and check the product label and local electrical code before installation.

Service and safe deployment

  • Verify voltage, phase, inlet plug, circuit ampacity, continuous load and per-outlet ratings against the PDU nameplate and the exact product manual.
  • Use grounded, correctly protected service; never defeat the protective-earth conductor, overload an outlet/bank, or daisy-chain power strips/PDUs.
  • Mount the chassis using the manufacturer-approved brackets and preserve ventilation and strain relief. Inspect cord, plugs, receptacles and enclosure for heat, wear or damage.
  • Disconnect upstream power before installation, relocation or service. Do not open energized mains equipment; use a qualified electrician where required.
  • Network management can switch power to connected systems; isolate management access, set unique credentials and verify firmware before deployment.

Manufacturer sources and manual

  1. Manufacturer product page — CyberPower PDU41023 Switched PDUManufacturer model listing and configuration details; match the complete SKU and region.
  2. Manufacturer documentation — PDU41023 User ManualManufacturer manual, technical data or specifications; use the revision applicable to the unit label and follow its installation and safety directions.