[ NETWORKED / SWITCHED RACK PDU // EXACT SKU ]
CyberPower PDU41009 Switched PDU
200–240 V single-phase, 30 A input (24 A continuous); 10 switched C19 outlets; 2U. This static record covers the named model only; confirm complete regional suffix, revision and nameplate before installation.
ARCHIVAL IDENTIFICATION: PDU41009. Record the complete label, serial/date code, firmware and condition; similarly named models are not electrically interchangeable.
Exact model specifications
| SKU / topology | PDU41009 — networked switched rack power distribution unit; no UPS battery or stored runtime. |
|---|---|
| Input and output voltage | 200–240 V AC input and output |
| Phase / ampacity | Single phase; 30 A input, 24 A maximum continuous load (derated) |
| Outlet count and type | 10 × IEC 60320 C19 outlets; individually switchable |
| Metering / outlet switching | Outlet-level switching plus local/network input and load monitoring; 20 A overcurrent protection per bank. |
| Network management | RJ45 Ethernet management with browser console and SNMP-based functions; set secure credentials and restrict management-network access. |
| Rack dimensions | 2U horizontal rackmount; nominal 19-inch rack width; approx. 17.05 × 4.41 × 3.5 in (W×D×H). |
| Plug and load compatibility | Attached NEMA L6-30P grounded plug requires a matching 200–240 V single-phase L6-30R. C19 receptacles mate with C20 equipment inlets; verify cord, equipment and circuit ratings. |
| Electrical safety | Continuous input load limited to 24 A despite the 30 A plug. Respect the per-bank 20 A protection and ensure equipment is rated for 200–240 V. Do not defeat grounding or daisy-chain PDUs; inspect cord and receptacles for heat or damage. |
Service and safe deployment
- Verify voltage, phase, inlet plug, circuit ampacity, continuous load and per-outlet ratings against the PDU nameplate and the exact product manual.
- Use grounded, correctly protected service; never defeat the protective-earth conductor, overload an outlet/bank, or daisy-chain power strips/PDUs.
- Mount the chassis using the manufacturer-approved brackets and preserve ventilation and strain relief. Inspect cord, plugs, receptacles and enclosure for heat, wear or damage.
- Disconnect upstream power before installation, relocation or service. Do not open energized mains equipment; use a qualified electrician where required.
- Network management can switch power to connected systems; isolate management access, set unique credentials and verify firmware before deployment.
Manufacturer sources and manual
- Manufacturer product page — CyberPower PDU41009 Switched PDUManufacturer model listing and configuration details; match the complete SKU and region.
- Manufacturer documentation — PDU41007/41008/41009 Series product documentationManufacturer manual, technical data or specifications; use the revision applicable to the unit label and follow its installation and safety directions.