Smart-UPS On-Line SRT10KXLT

APC / Schneider Electric SRT10KXLT: 10000 VA / 10000 W online double-conversion UPS. This record covers only the identified SKU and regional configuration; match complete model code and nameplate to manufacturer documentation.

Original local functional schematic for SRT10KXLT, not a product photograph or wiring diagram
LOCAL FUNCTIONAL SCHEMATIC // NOT TO SCALE

ARCHIVAL IDENTIFICATION: Record full SKU, region, serial/date code, firmware/revision, installed options, battery identifier and observed condition. Similar product names do not prove electrical compatibility.

Model specifications

Exact model / topologyAPC / Schneider Electric SRT10KXLT; Online double-conversion UPS for 208 V single-phase service.
Rated output10000 VA / 10000 W. VA and W limits are separate constraints; never exceed either.
Input / output voltageInput: 208 V nominal; hardwired input. Output: 208 V nominal output; confirm exact site wiring and configuration before connection.
Input connectionHardwired input connection (no plug/receptacle); requires a correctly rated 208 V circuit.
Output receptacles4 × NEMA L6-20R and 2 × NEMA L6-30R output receptacles.
Battery chemistry / serviceInternal sealed lead-acid battery system; supports compatible SRT external battery packs for additional runtime. Match the complete SKU and approved battery service instructions.
RuntimeThe manufacturer SRT8K/SRT10K guide and runtime documentation give load- and pack-dependent values. Actual runtime is affected by battery condition/age, charge, temperature and connected watts.
Transfer behaviorOnline double-conversion keeps the inverter as the normal load source; no utility-to-inverter transfer interval in normal operation. Bypass and protection transitions have defined operating limits in the manual.
Communications / compatibilityUSB/serial communications and SmartSlot for compatible optional network management accessories; confirm management card and shutdown software support.
Compatibility / safety208 V, 10 kVA/10 kW system with hardwired input and L6-20R/L6-30R outputs. Dedicated rated wiring, grounding and overcurrent protection are essential; have installation and service performed by qualified personnel. Read the exact revision of the manufacturer manual before connection, service or battery replacement.

Service and compatibility notes

  • Measure and record connected watts and source voltage; runtime is not guaranteed for an aged or untested battery.
  • Do not open energized mains equipment. Never defeat protective earth, overload an outlet, use damaged equipment, or substitute an unapproved battery.
  • For hardwired or high-current versions, qualified installation, rated branch protection and local electrical code apply.
  • Confirm the complete model suffix, input wiring, output voltage, outlet map and manual revision against the unit nameplate before connecting equipment.

Manufacturer datasheet and manual sources

  1. APC Smart-UPS On-Line SRT10KXLT manufacturer specificationOfficial Schneider Electric SKU page for power, 208 V connections, outlets and options.
  2. APC SRT8K/SRT10K tower/rack installation guideOfficial manufacturer guide covering installation, wiring and safety.