ALIENCULTIST.COM
HARDWARE ARCHIVES // PART RECORD

[ BACNET POWER METER // ACUVIM IIBN ]

Accuenergy Acuvim IIBN

Panel power and energy meter with BACnet/IP for building automation. The IIBN is a metering instrument; CT or sensor option, display package and communication configuration must be confirmed against the purchased unit.

Original Accuenergy Acuvim IIBN panel meter and BACnet network schematic
LOCAL FUNCTIONAL SCHEMATIC // NOT A WIRING DIAGRAM

VARIANT CONTROL: Metering current input depends on the selected CT/sensor and order configuration. Do not assume a bundled sensor or panel cutout without checking the order documents.

Specifications & compatibility

Exact model / functionAccuenergy Acuvim IIBN BACnet Power and Energy Meter.
Measured metricsMore than 100 metering parameters are available across the family, including electrical quantities and power-quality data; enabled parameters depend on configuration.
Voltage / phaseDirect voltage measurement to 400 V line-to-neutral / 690 V line-to-line; compatible system and phase configuration must follow the manual.
Current range / accuracyCurrent range depends on the ordered current input and selected CT/sensor. Manufacturer lists ANSI C12.20 Class 0.2 / IEC 62053-22 Class 0.2s energy accuracy for the IIBN; confirm the exact setup and metric.
Display / network / outputPanel digital display configuration; BACnet/IP and embedded web-server access. Confirm display option on the order code.
Form factorPanel-mounted meter; exact mounting and enclosure configuration depend on ordered package.
Host compatibilityBACnet/IP-compatible building automation controller or monitoring host; no operating-system-specific desktop host is required.
Electrical safetyUse the correct current sensor and voltage wiring method from the Acuvim IIBN manual. Qualified personnel must isolate and verify circuits before installation; no safety protection is implied by meter accuracy or BACnet connectivity.

Installation & archival notes

  • Retain the exact order code, input/sensor option, BACnet instance/address and firmware with measurements.
  • Use manufacturer-approved sensors and respect their separate voltage, current and safety categories.
  • Do not open energized equipment; install in an appropriately rated panel.

Manufacturer sources

  1. Accuenergy — Acuvim IIBN product pageModel identity, BACnet features and product configuration information.
  2. Accuenergy — Acuvim IIBN datasheetMeasurement functions, voltage range and accuracy class.
  3. Accuenergy — product support documentsManufacturer manuals and configuration reference; use the IIBN revision corresponding to the installed unit.